Generators & fuel · Worked example

A delivery record and a tank reading tell different stories.

The facilities team has a 1,000 litre delivery note. The bulk-tank indication rises by 870 litres. The gross difference is 130 litres before recorded outflows. Trace the measurement window, fuel movements and records behind both numbers before deciding what it means.

Authored example inputs for exploring an investigation. These are not readings from a customer installation. Change the numbers and evidence selections to see how the next checks change.

Follow the fuel. Then follow the records.

One boundary: the bulk tank between its before and after readings. A transfer to a day tank leaves this boundary. Fuel consumed later from that day tank must not be counted again as direct bulk consumption.

The physical path and the evidence path

Schematic · Not an installation design
Fuel delivery, bulk tank, day tank and generatorDelivery enters the bulk tank. Direct consumption and net transfer to a day tank are separate outflows. Onward day-tank consumption is excluded from this bulk-tank arithmetic. Dashed lines connect equipment to the evidence review. BULK-TANK BOUNDARY Delivery record1,000 L Indicated rise870 L DIRECT BULK CONSUMPTION0 L entered 0 L transferred DAY TANKGENERATOR ONWARD USE: DO NOT COUNT TWICE Time-aligned evidence review
Solid arrows show possible fuel paths; dashed lines show records to connect. Equipment drawing is fixed, not a live level display. Numeric labels follow your entries.

1. Enter the record quantities

Litres, for the same before/after window. Up to three decimal places; the input limit is for this example, not a tank capacity.

A zero is an entered quantity, not evidence that no fuel moved. Direct consumption excludes fuel already counted in a transfer. This simple example covers net outward movements only; a tank decrease or reverse flow needs a fuller record review.

2. Select evidence you would need

Each selection is your assertion for exploring the example. The page does not retrieve, inspect or verify documents.

3. Read the difference, with its limits

Arithmetic updates from your entries. No physical tolerance is applied.

Residual remains after entered outflows
Gross difference before recorded outflows130 L
Rise + entered outflows870 L
Signed residual after entered outflows130 L

1,000 − 870 − 0 − 0 = 130 L

Accounted record quantities: indicated rise, direct consumption and net transfer out.

130 L remains between the delivery record and the entered quantities. Check the records before drawing a conclusion.

Entered numbers and evidence selections are user assertions. This page has not verified supporting records. Arithmetic agreement does not validate physical quantities, establish a cause or approve operation. Engineering review remains.

Next checks from these selections

  • Check the delivery record, units and receiving tank.
  • Align before/after readings, delivery and outflow records to one time window.
  • Review the level-to-volume conversion and relevant calibration evidence.
  • Check consumption and transfer records, including evidence for any entered zero.
  • Confirm the bulk-tank boundary and exclude double-counted downstream consumption.

Start with a time-aligned record review before specifying additional equipment.

What the facilities team would gather

The first two quantities are supplied as example inputs. The rest of the evidence is deliberately open. Ticking a box above changes the worked interpretation; it does not create these records.

Example evidence register and its decision limits
Record or observationStarting positionWhat to establish
Delivery note1,000 L enteredRecord identity, units, receiving tank and delivery start/end times.
Bulk-tank indication870 L rise enteredOriginal before/after readings, timestamps, conversion method and instrument evidence.
Direct consumption0 L entered; supporting records openMeasured or documented quantity for this window; runtime alone is not a measured volume.
Day-tank transfer0 L entered; supporting records openNet transfer leaving the bulk tank. Exclude onward consumption already inside that transfer.
Clock alignmentNo source timestamps suppliedIdentify gaps and conflicting clocks before comparing records.
Measurement basisNo calibration records suppliedCheck instrument identity, tank conversion and suitability of the measurement evidence.
Record integration

When events cannot be joined

Connect delivery, transfer and generator records around agreed asset IDs and timestamps. A possible output is a traceable event register with gaps and conflicting records visible.

Sensing & electronics

When a quantity is not supported

Review existing instruments and conversion records first. If a measurement gap remains, scope sensing or logging around the tank and fuel paths. Selection and validation depend on the actual equipment.

Engineering review

When the arithmetic agrees

Retain the source records and measurement limits. An arithmetically balanced set of entered quantities can support a focused review; it cannot establish physical certainty or replace the authorised team's operating procedures.

Bring the discrepancy and the records you have.

A useful starting brief names the tank, delivery window, available readings and the decision the team needs to make. Unknowns can stay unknown.